Pumps don't actually suck fluid. They create a low-pressure zone at the inlet, and atmospheric pressure (plus any elevation head) pushes fluid in. If the inlet pressure drops below the fluid's vapor pressure, the liquid flashes to vapor inside the pump — the bubbles collapse violently on the impeller, and you get cavitation damage, noise, and lost flow. NPSH (Net Positive Suction Head) is the bookkeeping engineers use to make sure this doesn't happen.
Two values matter:
The rule: NPSHa > NPSHr, with a safety margin of typically 0.6 m (2 ft) or 10–20%, whichever is larger.
The NPSHa equation, all in head units (meters or feet of fluid):
NPSHa = Hatm + Hstatic − Hfriction − Hvapor
Worked example: pumping 60°C water from an open tank 3 m below the pump, with 1.5 m of friction loss in the suction line. Vapor pressure of water at 60°C is ~2.0 m.
NPSHa = 10.3 − 3.0 − 1.5 − 2.0 = 3.8 m
If the pump curve says NPSHr = 3.5 m at your flow, you have only 0.3 m of margin — below the typical safety buffer. Options: lower the pump, fatten the suction pipe (less friction), cool the fluid, or pick a pump with lower NPSHr.